KEBOS GH11 2KVA/1800W Online Double Conversion, Tower UPS

25,000.00

Description

GH11 2KVA-  is specifically designed for operation in poor power areas. They provide high power density with long backup time in compact size. It’s ideal for ATMs, banking, and other business-critical applications. Users also can adjust the charging current from 1A to 6A according to different applications.

1kva 2kva 3kva 6kva 10kva 110v 220v Online Backup Ups Price - Buy ...

 

MODEL: GH11-2KVA

FEATURES

  • True double-conversion
  • Microprocessor control optimizes reliability
  • Input power factor correction
  • Output power factor 0.9
  • Wide input voltage (110 V – 300 V)
  • Converter mode available
  • ECO mode for energy saving( Only available for 1-3KVA)
  • Generator compatible
  • Adjustable charging current via LCD or software(1A-6A) only available for 6K/10K models
  • Smart SNMP works well with either USB or RS-232 together
  • Comprehensive display allows easy monitoring and access of UPS status

SPECIFICATIONS:

MODE GH11-2K (L)
PHASE Single phase with ground
CAPACITY 2000 VA / 1800 W
INPUT
Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Input Voltage Range 55-145VAC or 110-300VAC at 50% load 85-140VAC or 160-280VAC at 100% load
Frequency Range 40-60Hz / 50-70Hz
Power Factor ≧0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC
Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 47-53Hz or 57-63Hz
Frequency Range (Batt. Mode) 50Hz±0.25Hz or 60Hz±0.3Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
Transfer Time
AC to DC Zero
Inverter to Bypass 4 ms (Typical)
Wave Form (Batt. Mode) Pure Sine wave
EFFICIENCY
To AC Mode 89%
To Battery Mode 87%

BATTERY
Battery Type 12V9AH
Numbers 4
Standard Model
Typical Recharge Time 3 hours recover to 90-100% capacity
Charging Current (max.) 1.0 A
Charging Voltage 54.7 VDC ±1%
Battery Type
Numbers 6

INDICATORS
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding

Warranty: