Description
Eaton 9SX (15kVA-20kVA) UPS
The new Eaton 9SX 15 kVA / 20 kVA UPS provides stable power for critical IT infrastructure, Edge computing, Industrial devices and Medical applications.
Advanced design combines superior efficiency, compact form factor, flexible wiring and maximum performance, even in challenging environments.
Eaton 9SX (15kVA-20kVA) – Features
- High efficiency with double conversion mode efficiency up to 96%
- ESS mode efficiency up to 98.8% with break time less than 2ms
- Unity power factor: Powers more servers than similar UPSs with equivalent VA ratings and lower power factors
- Intelligent Power Management Software which is compatible with all major OS including virtualization software such as VMware and Hyper-V
- Support Eaton Network-M2 card certified by UL 2900-2-2 and IEC cyber security standards
- High power density and reduces rack space
- Flexible input and output wiring configuration in 3:3, 3:1, 1:1 which enables easy stock to catch up with fast deployed edge computing market
- Large LCD touch screen with built-in gravity sensor assures fast installation
- Eaton’s exclusive ABM® technology increases battery service life by 50%
Eaton 9SX 20kVA RT3U
General | |
Topology | Double conversion |
Configuration | Rack/Tower |
Part Number | 9SX20KPM |
Rating (VA/Watts) | 20000/20000 |
Dimensions (H x W x D, mm) | 129 x 438 x 589 |
Weight (kg) | 23.7 |
Warranty | 3 Years |
Electrical Input | |
Connection |
Hardwired – see manual for terminal block layout
|
Input Voltage Range | 160V~300V full load; 100~160V linear derating |
Nominal Voltage | 1 phase 220/230/240V; 3 phase 380/400/415V |
Frequency | 50/60 Hz autoselection |
Frequency Range | 40-70 Hz |
Input Power Factor | 1 |
THDI | ≤3% linear load; ≤5% non-linear load |
Electrical Output | |
Voltages | 1 phase 220/230/240V; 3 phase 380/400/415V |
Voltage THD | ≤1% linear load; ≤3% non-linear load |
Output Receptacles |
Hardwired – see manual for terminal block layout
|
Overload Capacity | 105%<load≤125%: 1min<br=””> 125%<load≤150%: 30s<br=””> >150%: 0.5s </load≤150%:></load≤125%:> |
Efficiency (Normal Mode) | Up to 96% in Online mode, up to 98.8% in ECO or ESS mode |
Output Frequency | 50/60 Hz autoselect |
Load Crest Factor | ≥3:1 |
Battery Management | ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Extended Battery Capability | EBM |
Communications | |
User Interface | Touchscreen color LCD (with gravity sensor) |
Communication Ports | RS232 DB9; USB 2.0 type-B; programmable dry in/out; Intelligent slot |
Communication Slot | 1 slot for Network-M2 or INDGW-M2 card. |
Environmental & Standards | |
Audible Noise | ≤55dB |
Operating Temperature | 0°C ~ 50 °C (0~40 no derating,40°C~ 50°C derating to 50%) |
Safety markings | CE/TLC/RCM |
Reviews
There are no reviews yet.