Description
HT11 series is online double-conversion UPS with full DSP control technology. With high input and output power factor, self-adjusting output frequency and network management, HT11 is a perfect choice for computers, telecommunication equipment and other sensitive devices.
SPECIFICATIONS
INVT HT1102S
Capacity 2KVA
Wattage 1800
Phase Single Phase in, Single Phase out
Input voltage 110VAC-288VAC
100% load@>176VAC; 80% load@>154VAC;
70% load@>132VAC; 50% load@>110VAC
Input PF ≥0.97
Input Frequency 40Hz~70Hz
Output PF 0.9
Output Voltage 220V/230V/240V
Voltage Regulation ± 1 %
THDu ≤2% THD, Linear Load
≤ 5% THD, None-linear
Crest Ratio 3:1
Efficiency 91.0%
<45dB@<70%Load,
<50dB@>70%Load
Overload Capability
Inverter 105%~130%: to bypass after 1 min;
150%: to bypass after 30Sec
Battery
105%~130%:shutdown after 10Sec;
150%:shutdown after 5Sec
Battery Voltage 72VDC
Battery type/Number 12V/7Ah*6
Max Charging Current 1A
Interface RS232,EPO
Optional Intelligent kits, USB(B Type),SNMP, dry contact ,Surge protection
W*D*H(mm) 190*374*336
Weight(Kg) 17
Warranty 2 Years /1 Year Battery
Reviews
There are no reviews yet.