Description
APC Smart-UPS SRT 3000VA 230V
SRT3000XLI
SRT3000XLI Features
APC Smart-UPS SRT 3000VA 230V
-
Battery failure notificationProvides early-warning fault analysis on batteries enabling timely preventive maintenance
-
ECO ModeOperating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
-
Green modePatent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
-
LCD graphics displayText and mimic diagrams that display modes of operation, system parameters and alarms.
-
Rack/Tower convertibleProtects the initial investment in the UPS when migrating from tower to rack-mount environment.
Smart-UPS On-Line Features & Benefits
Marketing Features
-
Save time with easy and convenient remote/network accessibility.Network manageable via serial, USB or Ethernet. Includes Powerchute® Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.
-
Peace of mind that comes with full equipment compatibility and reliability of a leaderProvides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.
-
Avoids costly power problems by keeping your IT equipment and data protected and available.Network grade power conditioning protects from damaging surges and disruptive noise. The double conversion architecture provides tight voltage regulation, frequency regulation ,and zero transfer time to battery during power events.
-
Low operating and maintenance costs with proven reliability and intelligent battery management.Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature compensated charging. Automatic self tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy to connect, hot-swappable battery modules provide battery replacement without powering down.
Protection
-
Frequency and voltage regulationGives higher application availability by correcting poor frequency and voltage conditions without using the battery.
-
Power conditioningProtects connected loads from surges, spikes, lightning, and other power disturbances.
-
Cold-start capableProvides temporary battery power when the utility power is out.
-
Safety-agency approvedEnsures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
-
Resettable circuit breakerEasy recovery from overloads; no need to replace a fuse.
-
Input power factor correctionMinimizes installation costs by enabling the use of smaller generators and cabling.
-
Generator compatibleEnsures clean, uninterrupted power to protected equipment when generator power is used.
Serviceability
-
Disconnected battery notificationWarns when a battery is not available to provide backup power.
-
Audible alarmsProvides notification of changing utility power and UPS power conditions
-
Automatic self-testPeriodic battery self-test ensures early detection of a battery that needs to be replaced.
-
User-replaceable batteriesIncreases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
-
Predicitive failure notificationProvides early-warning fault analysis ensuring proactive component replacement.
Adaptability
-
Plug-and-Play external batteriesEnsures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
-
Rack/Tower convertibleProtects the initial investment in the UPS when migrating from tower to rack-mount environment.
-
Flash upgradeable firmwareInstall maintenance releases of firmware remotely using FTP.
Manageability
-
Serial connectivityProvides management of the UPS via a serial port.
-
Network manageableProvides remote power management of the UPS over the network.
-
InfraStruXure Manager CompatibleEnables centralized management via the APC InfraStruXure Manager.
-
SmartSlotCustomize UPS capabilities with management cards.
-
LED status indicatorsQuickly understand unit and power status with visual indicators.
Availability
-
Scalable runtimeAllows additional run time to be quickly added as needed.
-
Intelligent battery managementMaximizes battery performance, life, and reliability through intelligent, precision charging.
-
Temperature-compensated battery chargingProlongs battery life by regulating the charge voltage according to battery temperature.
-
Automatic internal bypassSupplies utility power to the connected loads in the event of a UPS power overload or fault.
-
Hot-swappable batteriesEnsures clean, uninterrupted power to protected equipment while batteries are being replaced
-
Automatic restart of loads after UPS shutdownAutomatically starts up the connected equipment upon the return of utility power.
Output
-
Output power capacity
2.7 KWatts / 3.0 kVA
-
Max Configurable Power (Watts)
2.7 KWatts / 3.0 kVA
-
Nominal Output Voltage
230V
-
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
-
Output Voltage Distortion
Less than 2%
-
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
-
Other Output Voltages
220, 240
-
Load Crest Factor
3 : 1
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Output Connections(8) IEC 320 C13 (Battery Backup)(2) IEC Jumpers (Battery Backup)(2) IEC 320 C19 (Battery Backup)
-
Bypass
Internal Bypass (Automatic and Manual)
Input
-
Nominal Input Voltage
230V
-
Input frequency
40 – 70 Hz (auto sensing)
-
Input Connections
British BS1363A, IEC-320 C20, Schuko CEE 7/EU1-16P
-
Cord Length
2.44meters
-
Input voltage range for main operations
160 – 275V
-
Input voltage adjustable range for mains operation
100 – 275 (half load)V
-
Number of Power Cords
3
-
Other Input Voltages
220, 240
Batteries & Runtime
-
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
-
Typical recharge time
3hour(s)
-
Nominal Battery Voltage
96V
-
Replacement Battery
-
Expected Battery Life (years)
3 – 5
-
RBC Quantity
1
-
Extendable Run Time
1
-
Extended Run Options
-
Runtime
-
Efficiency
Communications & Management
-
Interface Port(s)
RJ-45 Serial , Smart-Slot , USB
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Audible and visible alarms prioritized by severity
-
Emergency Power Off (EPO)
Yes
-
Available SmartSlot™ Interface Quantity
1
Surge Protection and Filtering
-
Surge energy rating
340Joules
-
Filtering
—
Physical
-
Maximum Height
432mm , 43.2CM
-
Maximum Width
85mm , 8.5CM
-
Maximum Depth
635mm , 63.5CM
-
Net Weight
31.3KG
-
Shipping weight
36.74KG
-
Shipping Height
246mm , 24.6CM
-
Shipping Width
599mm , 59.9CM
-
Shipping Depth
871mm , 87.1CM
-
Color
Black
-
Units per Pallet
6.0
Environmental
-
Operating Temperature
0 – 40 °C
-
Operating Relative Humidity
0 – 95% non-condensing %
-
Operating Elevation
0-3000meters
-
Storage Temperature
-15 – 45 °C
-
Storage Relative Humidity
0 – 95% non-condensing %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
55.0dBA
-
Online thermal dissipation
703.0BTU/hr
-
Protection Class
IP 20
Conformance
-
Approvals
CE, CE Mark, EAC, EN/IEC 62040-1, EN/IEC 62040-2, RCM, VDE
-
Standard warranty
3 years repair or replace (excluding battery) and 2 years for battery