Description
Eaton 9130 1000VA Tower
103006434-6591
Warranty 3 Years Hardware /2 years Battery
Features
• Protects against downtime, data loss and process interruption
by providing continuous, clean power
• Offers premium performance with a 0.9 power factor and
>95 percent efficiency
• Increases battery service life and system uptime with-
ABM™ battery charging technology
• Enables prolonged runtime of essential equipment during
power outages by allowing for orderly, remote shutdown
of non-critical systems or processes by Load Segment
Control
• Provides installation flexibility with a choice of rack or
tower designs, both conserving valuable space
• Enhanced monitoring and configuration capability through
easily navigated multilingual graphical display
The Eaton® 9130 UPS, Powerware
® series, resolves utility
power problems and delivers
superior power protection for
IT and networking equipment,
medical systems, manufacturing
process control—or anywhere
critical equipment and
applications require clean,
continuous power
Double-conversion
design for superior
power protection
The 9130 is constantly monitoring
power conditions—
regulating both voltage and
frequency. Even when presented
with the most severe
power problems, this UPS’s
output remains within three
percent of nominal voltage.
High efficiency. The more
efficient the UPS, the lower
your utility and cooling bills.
When power conditions are
within acceptable limits, the
9130 can operate in a highefficiency
mode providing 95
percent or higher efficiency.
Advanced power protection for:
• IT and networking environments
• Servers, networking gear
• Telecommunications, VoIP, security systems
• Medical systems
• Diagnostics and medical screening
• Patient record archives
• Manufacturing systems
• Chip fabrication
• Pharmaceutical production
• Chemical processing
General | |
Topology | Online, double-conversion |
Configuration | Tower |
Part Number | 103006434-6591 |
Color | Black |
Rating (VA/Watts) | 1000/900 |
Diagnostics | Full system self-test |
UPS Bypass | Automatic bypass |
Dimensions (H x W x D, mm) | 230 x 160 x380 |
Weight (kg) | 14.5 |
Remote Emergency Power off (REPO) | Emergency shutdown control through the REPO port |
Efficiency | 94% in high-efficiency mode; 90% in online mode |
Electrical Input | |
Connection |
(1) IEC-320-C14
|
Input Cord | Schuko 10A to IEC 320-10A |
Input Voltage Range | 180-276 Vac (with load PF of 0.7) |
Nominal Voltage | 220–240V |
Frequency | 50/60 Hz |
Frequency Range | 45–65 Hz |
Nominal Current | 4.3A @230V |
Breaker Ratings | 10A |
Electrical Output | |
Outlets |
(6) IEC-320-C13
|
On Utility Voltage Regulation | ±3% of nominal |
On Battery Voltage Regulation | ±3% of nominal |
Power Factor | 0.9 |
Frequency Regulation | ±3% Hz online |
Load Crest Factor | 3 to 1 |
Battery | |
Battery Description | VRLA 12V/9 Ah (internal and External) |
Battery Type | Replaceable maintenance free sealed lead acid |
Battery Replacement | Hot-swappable internal batteries |
Start On Battery | Allows start of UPS without utility input |
Communications | |
User Interface | Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
LEDs | Four status-indicating LEDs |
Communication Ports | RS-232 and USB HID port as standard |
Relay Output | Common alarm standard |
Communications Card Slots | Optional SNMP/Web card for monitoring in SNMP-based networks, monitoring through Web browser interface. Relay card for integration to industrial environment and BMS, remote shutdown for IBM AS/400 systems |
Environmental & Standards | |
Heat Dissipation (BTU) | Line: 500, Bat: 674 |
Audible Noise | <44 dB |
Operating Temperature | 0˚C to +40˚C |
Performance – Safety – EMC | CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2), GS |
Storage Temperature | -20˚C to +40˚C with batteries and -25˚C to +55˚C without batteries |
Relative Humidity | 5–90% non-condensing |