Description
Eaton 9PX UPS
The Eaton 9PX UPS provides energy-efficient power protection for small & medium Datacentres, IT rooms and Infrastructure. Delivering double conversion protection with 40% less energy usage and 28% more power 9PX is the perfect UPS for IT and Facility managers that are concerned by energy cost and are looking for next generation power protection solutions.
Eaton 9PX – Features
- Enables you to customize UPS settings, view load and power consumption information through the graphical interactive LCD screen interface
- Energy efficient (up to 95% in Online mode, 98% in high-efficiency mode)
- Next-generation graphical LCD display (7 languages)
- Provides more real power (watts) to protect more equipment with a 0.9 power factor
- Parallel operation using HotSync technology
- Maintenance ByPass available as an option
- Energy metering – kWh values can be monitored using the LCD or Eaton’s Intelligent Power Software Suite
- Compatible with Virtual environments (VMware, Hyper-V, Citrix Xen, Redhat)
General | ||
Topology | On-line double conversion with PFC (Power Factor Correction) system | |
Configuration | Rack/Tower | |
Part Number | 9PX8KiRT | |
Rating (VA/Watts) | 8000/7200 | |
Dimensions (H x W x D, mm) | 440 x 260 x 700 | |
Weight (kg) | 84 | |
Warranty |
|
|
Electrical Input | ||
Connection |
Hardwired – see manual for terminal block layout
|
|
Input Voltage Range | 176-276V without derating (up to 100–276V with derating) | |
Nominal Voltage | 200/208/220/230/240/250V | |
Frequency | 50/60 Hz autoselection | |
Frequency Range | 40-70 Hz | |
Short Circuit Current | 120 A | |
THDI | <5% | |
Electrical Output | ||
Voltages | 200/208/220/230/240/250V +/– 1% | |
Voltage THD | < 2% | |
Output Receptacles |
Hardwired – see manual for terminal block layout
|
|
Overload Capacity | 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms | |
Efficiency (Normal Mode) | Up to 95% in Online mode, 98% in Hi-Efficiency mode | |
Output Frequency | 50/60 Hz autoselect, frequency converter as standard | |
Load Crest Factor | 3:1 | |
Battery | ||
Battery Management | ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. | |
Extended Battery Capability | EBM (3U) | |
Communications | ||
User Interface | Multilingual graphical LCD display | |
Communication Ports | 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation. | |
Communication Slot | 1 slot for Network-MS card, ModBus-MS or Relay-MS cards | |
Environmental & Standards | ||
Audible Noise | <48dB | |
Operating Temperature | 0 to 40°C continuous | |
Safety markings | IEC/EN 62040-1, UL 1778, CSA 22.2 | |
EMC Markings | IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance) | |
Approvals | CE, CB report (TUV), UL | |
In the interests of continuous product improvement all specifications are subject to change without notice.
Reviews