Kebos Powergrade 100KVA/80KW 3PHASE 380VAC 60HZ Online Tower Ups Low Frequency UPS

123.00

Description

GL33 10K-200KVA

Low Frequency Online UPS GL33 10-200K embedded with output isolation transformer. GL33 series Online UPS will eliminate common mode noise and the need to install expensive dedicated circuits. It provides reliable galvanically isolated power to critical equipment.

 

 

FEATURES

  • Online double-conversion
  • DSP technology guarantees high reliability
  • True galvanic isolation transformer design
  • Control designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Independent ventilation enhance durable operation under harsh environment
  • Adjustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units (option)
  • Variety of communication options available
  • Reverse phase frequency operation and supports non-neutral input

 

SPECS

MODEL GL33-100KL
CAPACITY 100KVA /80KW

INPUT
Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph + N)
Acceptable Voltage Range 165VAC ~ 280VAC (Ph-N) ; 285VAC ~ 485VAC (Ph-Ph)
Frequency 50/60 Hz ± 10 %
Precision Stationary: ±1% Transitory: ±5% (load variations 100-0-100%)

Frequency
Max. Synchronisation Speed 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Waveform ±1 Hz/s
Total Harmonic Distortion (THDv) Pure Sinewave
Phase Displacement <2% (Linear Load) ;<5% (Non-linear Load) ;120º ±1% (balanced load) ;120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time 3 cycles at 90 % of the static value
Admissible Overload 110% for 10min; 150% for 60sec ; >160% for 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6~1 (inductive or capacitive)
Imbalance Output Voltage @ 100% Unbalanced Load <1%

Current Limit High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit

STATIC BYPASS
Type Solid state 176VAC ~ 264VAC (Ph-N) ; 304VAC
Frequency 50/60 Hz ± 10 %
Activation n Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear

MAINTENANCE BYPASS
Type Without interruption
Voltage Same as the bypass input
Frequency Same as the bypass input

Overall Line Mode 92%
Efficiency Battery Mode 93%

BATTERY & CHARGER
Battery Type and Numbers 12VDC x 32 pcs (29~32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries
Charging Method CC/CV
Precision ±1%
Charging Current Default 10A; Maximum 40A; 5A@ full load
Charging Voltage 432 VDC (Based on 32pcs batteries)

ALARM
Dimensions, D x W x H(mm) 975x554x1286
Net Weight (Kgs) 573

Warranty 1 Year