Description
Liebert GXT5 750VA – 20kVA
Vertiv™ Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers robust power outage protection and continuous power conditioning in a compact and flexible deployment system. Liebert GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications. Liebert GXT5 comes with various models ranging from 750VA to 20kVA and in both tower or rack form factor.
- Banking, Financial and Insurance
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Manufacturing
- Retail and Wholesale
- Telecom
- Transportation
Warranty: 3 Years Warranty
Technical Specifications
Ratings (VA/W) 16000 VA/16000 W
Dimensions, inches (mm) UnitWxDXH 16.9×24.8×15.5 (430×630×394)
Weight, pounds (kg) Unit 298 (135.2)
Input AC Parameters
Operating Frequency, Nom 50 or 60 Hz (Factory Default is 50 Hz )
Input Voltage 200/208/220/230/240 VAC Single Phase+ neutral + PE (or) 345/360/380/400/415 VAC Three phase + neutral + PE
Operating Voltage Range Without Battery Operation (VL-N)
176 to 288 VAC (100 to 176 VAC with power derating)
Input Frequency Without Battery Operation 40 to 70 Hz
Output AC Parameters
AC-AC Efficiency Up to 95.9%
User-configurable Voltage 200/208/220/230/240 VAC
Factory Default Voltage 230V
Frequency 50 Hz
Waveform Pure Sinewave
Main Mode Overload ≤ 105% continuous ; 105 to 125% for 5 minutes; 125 to 150% for 60 seconds; > 150% minimum 200 ms
Internal Battery
Charger Current 2.25 A (default), maximum 13 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 32x 12V x 9.0 AH
Back-up Time at Full Load 3.5 Min.
Back-up Time at Half Load 9.5 Min
Bypass Protection Limits
Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.
Lower -limit Selections – 10% – 15% -20%; default – 15%
Disable-bypass operation When the input frequency prevents synchronous operation
General
Operating Temperature Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature -20 to +60 °C ( contain batteries will be from -15 to 40 °C)
Relative Humidity 0 to 955 non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Nose <58 dBA
Safety
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A), CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated Susceptibility IEC/EN EN61000-4-3, Level, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation ISTA Procedure 1E
POD
Model Number PD5-CE10HDWRMBS
Amp Rating 63 A
Includes Four ICE320 C19 16 A / 250 V Sockets, Four C13 10 A / 250 V Sockets