Description
GXT5-10KIRT5UXLN
The Liebert® GXT5™ UPS is a single phase, online double conversion UPS solution which offers premium power outage protection and continuous power conditioning in a compact and flexible deployment system. The new Liebert® GXT5™ from Vertiv™ is an advanced version of the widely-regarded GXT UPS Series. GXT5 is ideally suited to protect critical infrastructure in both centralized and edge network applications.
- Banking, Financial and Insurance
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Manufacturing
- Retail and Wholesale
- Telecom
- Transportation
Warranty: 3 Years Warranty
Technical Information
Ratings (VA/W) 10,000VA / 10,000W
Dimensions and Weight
Dimensions (mm) Unit, W×D×H 430×630×217
Unit Weight (kg) 74.5
Input AC Parameters
Operating Frequency, Nom 50 or 60 Hz (Factory default is 50 Hz )
Factory Default Voltage 230 VAC
Operating Voltage Range Without Battery Operation 176 to 288 VAC (100 to 176 VAC with power derating) 176 to 288 VAC: (100 to 176 VAC with power derating) 288 VAC
Input Frequency : Without Battery Operation 40 to 70 Hz
Output AC Parameters
AC-AC Efficiency 95%
User-configurable Voltage 200/208/220/230/240 VAC
Factory Default Voltage 230 VAC
Factory Default Voltage 50 Hz or 60 Hz, Nominal
Waveform Pure Sinewave
Output Power Connection – Output Terminal Block
Main Mode Overload >150% minimum 200 ms, 125 – 150% for 60 seconds; 105 – 125% for 5 minutes; ≤ 105% continuous
Internal Battery
Charger Current 2.25 A (default), maximum 8 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating – 2×8 x12V x 90 AH
Back-up Time at Full Load 2
Back-up Time at Half Load 7
Bypass Protection Limits
Upper-limit Selections + 10%, + 15%, + 20%; default + 10%.
Lower – limit Selections – 10% – 15% -20% default – 15%
Disable-bypass Operation When the input frequency prevents synchronous operation
General
Operating Temperature, °C Full power up to 40 oC (up to 50 oC with derating)
Storage Temperature, °C – 15 to + 40
Relative Humidity – 0 – 95% non-considering
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating
Audible Noise – <55 dBA
Safety UL-1788 (Fifth Edition),C-UL listed, IEC 62040-1: 2017 Edition 2.0, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick EMC = IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) CISPR22 Class A (RFI)
ESD IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated Susceptibility – IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient- IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity: IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation ISTA Procedure 1E